Product presentation

Manufactured in our French factories, the ENERIUM range of power meters is specifically designed for energy management and electrical optimization in industrial sites and power grids.


Thanks to advanced measurement functions, they enable the analysis of power quality, the correlation of climate data with energy consumption, and the alerting of the user in case of critical electrical parameters being exceeded.

With a compact 144x144mm form factor that easily integrates into electrical cabinets, the ENERIUM 200 power meter is suitable for precise and accurate measurement ( accuracy class 0.2 s) of any HV/MV/LV electrical supply or supply.


Analyzing the behavior of the electrical installation is done in just a few clicks on the ENERIUM 200 screen: alarm log, Fresnel diagram, harmonic analysis by order, etc.

The integrated Ethernet or RS485 communication interfaces allow for remote operation and control of the product.

Its digital and analog inputs and outputs (up to 8) allow for easy integration into a monitoring or control architecture.

Class 0.2s

Class 0.2s

Standard

Standard

Harmonic disturbance meas.

Harmonic disturbance meas.

High-readability display

High-readability display

Available inputs/outputs

Available inputs/outputs

Contact a sales representative

Need information about our solutions? Our experts are available to advise you and assist you with your project. Contact a sales representative now for a detailed presentation and a quote tailored to your needs.

Contact a sales representative

Video

thumbnail

YouTube conditionne la lecture de ses vidéos au dépôt de cookies afin de vous proposer des publicités ciblées en fonction de votre navigation.

Pour plus d'information, visiter la politique « cookies » de YouTube.

Vous avez refusé ses cookies et donc ne pouvez pas visionner la vidéo.

En cliquant sur « Paramètres des cookies » vous pouvez modifier vos choix et accepter les cookies YouTube pour visualiser la vidéo.

Vous garder la possibilité de retirer votre consentement à tous moment.

Paramètres des cookies

MEMO & ENERIUM power monitors

Enerium and Memo power metering devices are essential tools for minimizing your energy consumption and optimizing your electrical installation in low, medium, or high voltage.

Highlights

RS485 or Ethernet communication as standard

Energy measurement class 0.2s

Wide choice of analog or digital inputs/outputs

Large ergonomic display

Made in France

Features

Electrical specifications. Electrical network

Maximum measured phase-to-phase voltage

650 kV

TT ratio

Primary TT: 100 V to 650 kV

Secondary VT: 100 V to 480 V

Max. measured current

25,000 A

CT ratio

Primary CT: 1 A to 25 000 A 

Secondary CT: 1 A or 5 A

Max. measured power

2 GW

Electrical specifications. Voltage inputs (AC)

Measurement range

From 5 to 130% of Vn for Vn = 57.7 / 230 V (ph-N) 

From 5 to 130% of Un for Un = 100 / 400 V (ph-ph)

Crest factor

2

Measurement accuracy (U and V)

0.2% from 20% to 130% of Un

.

Voltage swell

Transient U = 800 V for 24 hours.  

Permanent 130% of 400 V = 520 V

Frequency

50/60 Hz

Consumption

< 0.1 VA

Input impedance

1 MΩ

Electrical specifications. Current inputs (AC)

Measurement range

From 1% to 130% of In for In = 5 A

.

Crest factor

3

Measurement accuracy

0.2% of ≥ 10%... ≤ 130% 

0.5% of ≥ 5%... ≤ 10% 

1% from ≥ 1% to ≤ 5%

Acceptable overload

Transient I = 250 A for 1 second.  

130% of 5 A = 6.5 A continuous

Consumption

< 0.15 VA

Electrical specifications. Compliance with standards

CEI 62053-21/22

Active energy class 0.2 s

CEI 62053-23/24

Reactive energy class 0.5 s

CEI 61557-12

class 0.5 or class 0.2

PMD SD/SS

Active energy class 0.5 or active energy class 0.2.  

Reactive energy class 0.5

Electrical specifications. RS485 output

Connection

2 wire, half duplex

Protocol

ModBus / JBus RTU mode

Speed (configurable)

2400 - 4800 - 9600 - 19 200 - 34 800

Parity

Even, odd or no parity

Jbus addresses

1 to 247

Electrical specifications. ETHERNET output

Type

RJ45 - 8 points

Protocol

ModBus / TCP

Speed (configurable)

Compatible with 10, 100 and 1000 base T networks

Electrical specifications. Auxiliary power supply

Power supply

80 to 265 Vac (< 20 VA) 

42.5 to 69 Hz  

80 to 265 Vdc  

19 to 57 Vdc (< 10 W)

Electrical specifications. Inputs / outputs

Max number of inputs / outputs

8

Environmental specifications.

Temperature of use

-10 °C to +55 °C (K55 according to IEC 61557-12)

Operating humidity

95 % to 40 °C

Storage temperature

-25 °C to +70 °C

Mechanical specifications.

Assembly

Front panel

Size

144 x 144

Documentation and support

Language *

Contact support

Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.

Contact support

Contact support

Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.

Contact support

References and accessories

To fully meet your expectations, a range of accessories is available that is compatible with your equipment. Feel free to add them to your quote request to obtain a complete and tailored solution.

ENERIUM 100 Customizable Power metering device

ENERIUM 100 Customizable Power metering device

ENERIUM100-CFG

ENERIUM 100 Customizable Power metering device - Size 144x144mm - Individual harmonic analysis measurement - Reference standard IEC 61557-12 - Panel mounting - High-readability display - Accuracy class 0.2s

ENERIUM 110 Customizable Power metering device

ENERIUM 110 Customizable Power metering device

ENERIUM110-CFG

ENERIUM 110 Customizable Power metering device - Size 144x144mm - Individual harmonic analysis measurement - Reference standard IEC 61557-12 - Accuracy class 0.2s

ENERIUM 200 Customizable Power metering device

ENERIUM 200 Customizable Power metering device

ENERIUM200-CFG

ENERIUM 200 Customizable Power metering device - 144x144mm format - Individual harmonic analysis measurement - Reference standard IEC 61557-12 - Panel mounting - High-readability display - Accuracy class 0.2s

ENERIUM 210 Customizable Power metering device

ENERIUM 210 Customizable Power metering device

ENERIUM210-CFG

ENERIUM 210 Customizable Power metering device - 144x144mm format - Individual harmonic analysis measurement - Reference standard IEC 61557-12 - Accuracy class 0.2s

ENERIUM 100 Power metering device communication RS485

ENERIUM 100 Power metering device communication RS485

P01330831

ENERIUM 100 Power metering device - Size 144x144mm - Individual harmonic analysis - Modbus RS485 communication - Reference standard IEC 61557-12 - Panel mounting - High-readability display - Accuracy class 0.2s

ENERIUM 100 Power metering device communication RS485 +2DI +2DO

ENERIUM 100 Power metering device communication RS485 +2DI +2DO

P01330832

ENERIUM 100 Power metering device - Size 144x144mm - Individual harmonic analysis - Modbus RS485 communication - 2 digital inputs + 2 digital outputs - Reference standard IEC 61557-12 - Accuracy class 0.2s

ENERIUM 200 Power metering device communication RS485 +4DI +2AO

ENERIUM 200 Power metering device communication RS485 +4DI +2AO

P01330833

ENERIUM 200 Power metering device - Size 144x144mm - Individual harmonic analysis - Modbus RS485 communication - 4 digital inputs + 2 analog outputs - Reference standard IEC 61557-12 - Accuracy class 0.2s

ENERIUM 200 Power metering device communication Ethernet +2DI +2DO +2AO

ENERIUM 200 Power metering device communication Ethernet +2DI +2DO +2AO

P01330834

ENERIUM 200 Power metering device - Size 144x144mm - Individual harmonic analysis - Ethernet communication - 2 digital inputs/2 digital outputs + 2 analog outputs - Reference standard IEC 61557-12 - Accuracy class 0.2s

ENERIUM 210 Power metering device communication Ethernet +8DI

ENERIUM 210 Power metering device communication Ethernet +8DI

P01330835

ENERIUM 210 Power metering device - Size 144x144mm - Individual harmonic analysis - Ethernet communication - 8 digital inputs - Reference standard IEC 61557-12 - Accuracy class 0.2s

Request a quote

Add one or more products to your quote request in just a few clicks. Our teams will analyze your needs and get back to you quickly with a personalized offer tailored to your requirements.