T82N T
Analog transducer for physical electrical quantities ( °C ) - 1 analog output
T82N K3-qualified class 0.5 analog transducers designed for the most demanding environments such as the nuclear sector. They convert AC electrical quantities into a linear DC process signal in mA or mV as per the IEC 60688 standard.
The electrical connection can be made directly or via a socket for easy replacement, and they can be mounted on a panel or on a symmetrical/asymmetrical DIN rail.
The range is fully configurable on request and is divided into 6 models:
UAR 1210B AC voltage measurement:
IAR 1210B AC current measurement:
PAR 1232B Active Power measurement:
QAR 1232B reactive power measurement:
JAR 1211B phase angle measurement:
FAR 1210B Frequency measurement:
Analogue device
Certification
Nuclear environment
Standard
Contact a sales representative
Need information about our solutions? Our experts are available to advise you and assist you with your project. Contact a sales representative now for a detailed presentation and a quote tailored to your needs.
UAR1210B: AC voltage input effective IAR1210B: Input AC current effective PAR1232B: Input Active power QAR1232B: Input Reactive power FAR1210B: Frequency input JAR1211B: Phase angle input
Accuracy
Class 0.5 according to IEC 60688 April 2013
Response time
120 ms to 260 ms at 95%
Current range
From 0 to 20 mA
Voltage range
From 0 to 10 V
Range of use
± 10% from 100/√3 Vac to 440 Vac
± 20% from 24 to 125 Vdc
Consumption
≤ 3 VA from 100/√3 to 440 Vac
≤ 3 W from 24 to 125 Vdc
2014/30/EC (EMC) IEC 61326-1 (07/2013)
2006/95/CE CEI 61010-1 (01/2011)
CEI 60688 (04/2013)
CEI 60688 (04/2013)
CEI 60068-2-6 (04/2008) CEI 60068-2-27 (07/2009)
-10 °C to +60 °C
Up to 95% at 45°C
-25 °C to +70 °C
By screw terminals 2 x 2.5 mm² or 1 x 6 mm²
.IP20 according to IEC 60529
0.70 to 0.85 kg (baseplate: 0.25 kg)
Language *
Contact support
Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
Language *
Contact support
Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
To fully meet your expectations, a range of accessories is available that is compatible with your equipment. Feel free to add them to your quote request to obtain a complete and tailored solution.
FAR-CFG
T82N FAR 1210B Configurable analog frequency converter - 1 factory-built analog output - DIN rail or base mounting - IEC 60688 standard - Class 0.5 - K3 certification
IAR-CFG
T82N IAR 1210B Configurable AC analog current converter - 1 factory-built analog output - DIN rail or base mounting - IEC 60688 standard - Class 0.5 - K3 certification
JAR-CFG
T82N JAR 1211B Configurable analog phase angle converter - 1 factory-built analog output - DIN rail or base mounting - IEC 60688 standard - Class 0.5 - K3 certification
PAR-CFG
T82N PAR 1232B Configurable analog active power converter - 1 factory-built analog output - DIN rail or base mounting - IEC 60688 standard - Class 0.5 - K3 certification
QAR-CFG
T82N QAR 1232B Configurable analog reactive power converter - 1 factory-built analog output - DIN rail or base mounting - IEC 60688 standard - Class 0.5 - K3 certification
UAR-CFG
T82N UAR 1210B Configurable AC analog voltage converter - 1 factory-built analog output - DIN rail or base mounting - IEC 60688 standard - Class 0.5 - K3 certification
Request a quote
Add one or more products to your quote request in just a few clicks. Our teams will analyze your needs and get back to you quickly with a personalized offer tailored to your requirements.