ULYS TT-M Modbus
Energy meter for three-phase networks - Connection to CT - Modbus - MID
ULYS MD100-M is dedicated to measurement and rebilling of energy consumption on single-phase 230 Vac networks up to 100A. Compliant with the EN 50470-1 standard and MID-certified, it is particularly suitable for uses linked to camping sites, marinas, holiday rentals and datacenters, as well as in industry. Its compact dimensions (2 DIN modules) make it easy to install in an electrical control box or an energy supplier's outdoor junction box. Its pulse outputs can be connected to a data concentrator such as ELOG for remote data retrieval with a PC, using consumption supervision software such as E.ONLINE. ULYS MD100-M displays a large amount of information:
Its simplified display gives an instantaneous view of the main quantities on its backlit LCD screen and all the other quantities can also be displayed (in particular, using the touch sensitive keys on the front panel or the optical head for configuration). Main specifications:
Certification
Compact product
Contact a sales representative
Need information about our solutions? Our experts are available to advise you and assist you with your project. Contact a sales representative now for a detailed presentation and a quote tailored to your needs.
ULYS meters are the essential tool for a connected and highperformance metering plan.
. Covers all single-phase feeders up to 100A
· MID-certified - Accuracy class B
. Bidirectional metering -Consumption/generation
· Parameterizable total meter
. Partial metering
. Dual-tariff metering
· Display of all the instantaneous electrical quantities
. Navigation and parameter settings on front panel with touch-sensitive keys
· 2 pulse outputs with parameterizable weight
Type
Direct
Nominal current (In)
100 A
Starting current (Ist)
20 mA
Nominal voltage (Un)
230 Vac (-15 % / +10 %)
Consumption
≤ 2 W/Phase - ≤ 10 VA/Phase
Nominal frequency
50 Hz ±10%
T1
0 V
T2
230 Vac
Weight
10000 imp/kWh, /kVArh
Number
2 (kWh import / export)
Weight
10000 - 2000 - 1000 - 100 - 10 - 1 - 0.1 - 0.01 imp/kWh
Duration
Active energy
MID class B according to EN 50470-1-3
Ingress protection
IP51 front panel
Format
2 DIN modules
Power circuit connection
Screw terminal block for 35 mm² wires
Pulse output or communication connection
Max 1.5 mm²
Assembly
On 35 mm DIN rail
Weight
160 g
Operating temperature
-25 °C to +55 °C
Relative humidity in operation
≤ 75%
Language *
Contact support
Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
Language *
Contact support
Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
To fully meet your expectations, a range of accessories is available that is compatible with your equipment. Feel free to add them to your quote request to obtain a complete and tailored solution.
P01330760
ULYS MD100 DIN rail format energy sub-meter - 230Vac network measurement - Nominal current 100A - Compliant with European MID directive
Request a quote
Add one or more products to your quote request in just a few clicks. Our teams will analyze your needs and get back to you quickly with a personalized offer tailored to your requirements.