T82N T
Analog transducer for physical electrical quantities ( °C ) - 1 analog output
Multifunction digital transducer with 1 analog output for single-phase and balanced three-phase 3 or 4-wire networks
Measured quantities: Vac, Uac, Iac, P, Q, S, F, PF, phi, Cos phi, Tan phi, phiU, phiV
Accuracy: Class 0.1
Voltage inputs: 276 (ph-n) / 1 MV (ph-n) maximum primary voltage measured
Current input: 1 A and 5 A / 40,000 A maximum primary current measured
Analog output ratings: ± 20 mA, ± 10V
Transfer curves: Linear, 2-slope and quadratic
Response time: 50 ms
Auxiliary source: 80 to 265 Vac / Vdc or 19 to 58 Vdc
Operating frequency: 50 or 60 Hz
Communication protocols:
ModBus in RTU mode (optical head)
ModBus/JBUS in RTU mode (RS485)
ModBus/TCP in RTU mode (Ethernet)
Fully configurable with TRIADJUST2 software
Reference standard:
IEC 60688
IEC 61010-1
IEC 61326-1
IEC 61000-6-5
Standard
Electrical substation envt.
Easy programming
Available inputs/outputs
Contact a sales representative
Need information about our solutions? Our experts are available to advise you and assist you with your project. Contact a sales representative now for a detailed presentation and a quote tailored to your needs.
4 kV insulation
Configurable and modifiable: Via TRIADJUST 2 software
Adjustable accuracy in class 0.1 as per IEC 60688
Response time up to 50 ms
Operating temperatures
-10°C to +55°C
Storage temperature
-40°C to +70°C
Relative humidity
≤ 95% to 55 °C
Ingress protection code
IP20
Mechanical shocks
CEI 60068-2-27
Vibrations
CEI 60068-2-6
Free fall with packaging
NF H0042-1
Dimensions
60 x 81 x 120.5 mm
Nominal value
From 57.7 Vac to 276 Vac max
Frequency
50 Hz: 42,5… 57,7 Hz. 60 Hz: 51… 69 Hz
Max. measured primary voltage
1 MV (ph-ph)
Acceptable overloads
300 Vac permanent - 460 Vac / 10 s
Consumption
< 0.2 VA
Input impedance
400 kΩ
Nominal value
0 to 10 A max
Max. measured primary current
40,000 A
Acceptable overload
50 In / 1 s
Consumption
< 0.15 VA
High level
80 / 265 Vac (50/60 Hz) - 80 / 265 Vdc
Low level
19 / 58 Vdc
Consumption
High level: from 3.3 VA to 8.5 VA max. Low level: from 3.2 W to 5.5 W max.
Maximum number
1
Nominal values
Current: ± 1 mA, ± 5 mA, ± 20 mA or voltage: ± 1 V, ± 10 V
Exceeding
01/02/2025
Peak-to-peak residual wave
± 0.2% of Io(₁) or ± 0.2% of Uo(₁). Io(₁) = output current, Uo = output voltage
Response time
50 ms - 100 ms - 200 ms - 500 ms - 1 s
Transfer curve
Linear, 2 slopes or quadratic
Connection
USB (PC). Optics (product)
Protocol
MODBUS. RTU mode
Speed
38 400 bauds
Connection
RJ45
Protocol
MODBUS / TCP. RTU mode
Speed
10 base T
Connection
2 wires Half duplex
Protocol
MODBUS / JBUS. RTU mode
Speed
2,400 to 115,200 bauds
Language *
Contact support
Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
Language *
Contact support
Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.
To fully meet your expectations, a range of accessories is available that is compatible with your equipment. Feel free to add them to your quote request to obtain a complete and tailored solution.
P01380001
Triad 2 Model T101 programmable digital converter with high-level power supply - 1 analog output rated at 20mA - IEC 60688 standard - Class 0.1
P01380002
Triad 2 Model T101 programmable digital converter with high-level power supply - 1 analog output rated at 20mA - Tropicalized surface treatment - IEC 60688 standard - Class 0.1
P01380003
Triad 2 Model T101 programmable digital converter with low-level power supply - 1 analog output with 20mA range - IEC 60688 standard - Class 0.1
P01380004
Triad 2 Model T101 programmable digital converter with low-level power supply - 1 analog output rated at 20mA - Tropicalized surface treatment - IEC 60688 standard - Class 0.1
P01380005
Triad 2 Model T101 programmable digital converter with high-level power supply - 1 analog output with 10V range - IEC 60688 standard - Class 0.1
P01380006
Triad 2 Model T101 programmable digital converter with high-level power supply - 1 analog output with 10V range - Tropicalized surface treatment - IEC 60688 standard - Class 0.1
P01380007
Triad 2 Model T101 programmable digital converter with low-level power supply - 1 analog output with 10V range - IEC 60688 standard - Class 0.1
P01380008
Triad 2 Model T101 programmable digital converter with low-level power supply - 1 analog output with 10V range - Tropicalized surface treatment - IEC 60688 standard - Class 0.1
Request a quote
Add one or more products to your quote request in just a few clicks. Our teams will analyze your needs and get back to you quickly with a personalized offer tailored to your requirements.