Product presentation

Multifunction digital transducer with 4 analog outputs for single-phase, split-phaseand three-phase balanced or unbalanced 3 or 4-wire networks

Measured quantities: Vac, Uac, Iac, P, Q, S, F, PF, phi, Cos phi, Tan phi, phiU, phiV

Accuracy: Class 0.1

Voltage inputs: 480 (ph-ph) / 1 MV (ph-ph) maximum primary voltage measured

Current input: 1 A and 5 A / 40,000 A maximum primary current measured

Analog output ratings: ± 20 mA, ± 10V

Transfer curves: Linear, 2-slope and quadratic

Response time: 50 ms

Auxiliary source: 80 to 265 Vac / Vdc or 19 to 58 Vdc

Operating frequency: 50 or 60 Hz

Communication protocols:

ModBus in RTU mode (optical head)


ModBus/JBUS in RTU mode (RS485)


ModBus/TCP in RTU mode (Ethernet)

Fully configurable via TRIADJUST2 software

Reference standard: IEC 60688


IEC 61010-1


IEC 61326-1


IEC 61000-6-5

Standard

Standard

Electrical substation envt.

Electrical substation envt.

Easy programming

Easy programming

Available inputs/outputs

Available inputs/outputs

Contact a sales representative

Need information about our solutions? Our experts are available to advise you and assist you with your project. Contact a sales representative now for a detailed presentation and a quote tailored to your needs.

Contact a sales representative

Highlights

  • K3-qualified products
  • Totally analog
  • Configurable on request

Features

Environment and standards / Climatic (IEC 60068 2-1 / 2-2 / 2-30)

Operating temperatures

-10°C to +55°C

Storage temperature

-40°C to +70°C

Relative humidity

≤ 95% to 55 °C

Environment and standards / Mechanical (CEI 60068 2-6 / 2-27 / 2-29 / 2-32 / 2-63)

Ingress protection code

IP20

Mechanical shocks

CEI 60068-2-27

Vibrations

CEI 60068-2-6

Free fall with packaging

NF H0042-1

Dimensions

120 x 81 x 120.5 mm

Electrical specifications / Voltage input

Nominal value

From 57.7 Vac to 480 Vac max

Frequency

50 Hz: 42,5… 57,7 Hz. 60 Hz: 51… 69 Hz

Max. measured primary voltage

1 MV (ph-ph)

Acceptable overloads

520 Vac permanent - 800 Vac / 10 s

Consumption

< 0.2 VA

Input impedance

400 kΩ

Electrical specifications / Current inputs

Nominal value

0 to 10 A max

Max. measured primary current

40,000 A

Acceptable overload

50 In / 1 s

Consumption

< 0.15 VA

Electrical specifications / Auxiliary power supply

High level

80 / 265 Vac (50/60 Hz) - 80 / 265 Vdc

Low level

19 / 58 Vdc

Consumption

High level: from 9 VA to 20 VA max. Low level: from 5.5 W to 11 W max.

Electrical specifications / Analogue outputs

Maximum number

4

Nominal values

Current: ± 1 mA, ± 5 mA, ± 20 mA or voltage: ± 1 V, ± 10 V

Exceeding

01/02/2025

Peak-to-peak residual wave

± 0.2% of Io(₁) or ± 0.2% of Uo(₁). Io(₁) = output current, Uo = output voltage

Response time

50 ms - 100 ms - 200 ms - 500 ms - 1 s

Electrical specifications /

Transfer curve

Linear, 2 slopes or quadratic

Electrical specifications / Optical head communication

Connection

USB (PC). Optics (product)

Protocol

MODBUS. RTU mode

Speed

38 400 bauds

Electrical specifications / Ethernet communication

Connection

RJ45

Protocol

MODBUS / TCP. RTU mode

Speed

10 base T

Electrical specifications / RS485 communication

Connection

2 wires Half duplex

Protocol

MODBUS / JBUS. RTU mode

Speed

2,400 to 115,200 bauds

Documentation and support

Language *

Contact support

Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.

Contact support

Language *

Contact support

Have a question about using or installing your equipment? Our support team is available to provide you with quick and effective solutions. Contact support for personalized assistance.

Contact support

References and accessories

To fully meet your expectations, a range of accessories is available that is compatible with your equipment. Feel free to add them to your quote request to obtain a complete and tailored solution.

TRIAD2 T303 Digital transducer low level 3S analogiques 10V trop

TRIAD2 T303 Digital transducer low level 3S analogiques 10V trop

P01380130

Triad 2 Model T303 programmable digital converter with low-level power supply - 3 analog outputs, 10V range - Tropicalized surface treatment - IEC 60688 standard - Class 0.1

TRIAD2 T304 Digital transducer low level 4 analog outputs 10V

TRIAD2 T304 Digital transducer low level 4 analog outputs 10V

P01380131

Triad 2 Model T304 programmable digital converter with low-level power supply - 4 analog outputs, 10V range - IEC 60688 standard - Class 0.1

TRIAD2 T304 Digital transducer low level 4S analogiques 10V trop

TRIAD2 T304 Digital transducer low level 4S analogiques 10V trop

P01380132

Triad 2 Model T304 programmable digital converter with low-level power supply - 4 analog outputs, 10V range - Tropicalized surface treatment - IEC 60688 standard - Class 0.1

Request a quote

Add one or more products to your quote request in just a few clicks. Our teams will analyze your needs and get back to you quickly with a personalized offer tailored to your requirements.